50

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P706

Sequencer:

Action after

Stop/Start

transition or

Fault Restart

0

0 Restart at beginning of

sequence

Pointed by TB13x

1 Restart at beginning of current

seg

2 Start at beginning of prior

segment

3 Start at beginning of next

segment

P707

Sequencer:

Number of cycles

1

1 65535

1 = single scan; 65535 = continuous

loop

P708

Sequencer: Time

units/scaling

0

0 0.1

{sec}

6553.5

Setup units/scaling for all

sequencer time related parameters

1 1

{sec}

65535

2 1

{min}

65535

NOTE:

P708 rescales the following sequencer related parameters:

- Segment Times in current step: P712, P717, P722, P727, P732,

P737, P742, P747, P752, P757, P762, P767, P772, P777, P782,

P787, P792

- Sequence diagnostic/status: P561, P562

Segment #1

P710

Segment #1

Frequency

Setpoint

0.0

-500.0

{Hz}

500.0

If P112 = 1, negative sign forces

reverse direction

P711

Segment #1

Accel/Decel

Time

20.0

0.0

{sec} 3600.0

P712

Segment #1

Time in current

step

0.0

0

0.0

{P708}

6553.5

0

{P708}

65535

Scaling/units depend on P708

Skip segment if time = 0

P713

Segment #1

Digital Output

State

0

Bit0 Relay

bit = 0: OFF (De-energized)

bit = 1: ON (Energized)

The corresponding digital output/

relay must be set to accept value the

from the sequencer: P140, P142=27

Bit1 TB14

P714

Segment #1

TB30

Analog Output

Value

0.00

0.00

{VDC} 10.00

TB30 configuration parameter must

be set to accept this value: P150

= 10

Segment #2

P715

Segment #2

Frequency

Setpoint

0.0

-500.0

{Hz}

500.0

If P112 = 1, negative sign forces

reverse direction

P716

Segment #2

Accel/Decel Time

20.0

0.0

{sec} 3600.0

P717

Segment #2

Time in current

step

0.0

0

0.0

{P708}

6553.5

0

{P708}

65535

Scaling/units depend on P708

Skip segment if time = 0