Commissioning

4.5.2

I/O Setup Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P113

Auto/Manual

Control

0

0 Terminal Strip Control

The reference is dictated by the

settings and state of the TB-13x

terminals. If no AUTO reference has

been setup on the terminal strip then

reference control is dictated by P101.

1 Auto/Manual (CTRL button

select)

Allows the reference to be switched

between auto and manual using

the CTRL pushbutton on the drive

keypad. If the CTRL pushbutton

has selected AUTO reference but

no AUTO reference has been setup

on the terminal strip, then reference

control is dictated by P101.

2 Manual Control Only

Reference is dictated by P101

regardless of any AUTO source

that may be selected by the TB-13x

terminals.

NOTE

P113 is applicable to 15 HP (11kW) and higher models only.

P115

MOP Speed

Initialization at

Power-Up

0

0 Set to last MOP speed at

power up

1 Set to 0.0Hz at power up
2 Set to Preset #3 at power up

P120

Assertion Level

2

1 Low

P120 and the Assertion Level

switch must both match the desired

assertion level unless P100, P121…

P123 are all set to 0. Otherwise an

F.AL

fault will occur.

2 High