Troubleshooting and diagnostics, 3 fault messages – LEESON SM4 Series Flux Vector User Manual

Page 65

Advertising
background image

64

Troubleshooting and Diagnostics

64

5.3

Fault Messages

The messages below show how they will appear on the display when the drive trips. When

looking at the Fault History (P500), the F. will not appear in the fault message.

Fault

Cause

Remedy

(1)

f.AF

High Temperature fault

Drive is too hot inside

• Reduce drive load

• Improve cooling

f.AL

Assertion Level fault

• Assertion Level switch is

changed during operation

• P120 is changed during

operation

P100 or P121...P123 are set

to a value other than 0 and

P120 does not match the

Assertion Level Switch.

• Make sure the Assertion Level

switch and P120 are both set

for the type of input devices

being used, prior to setting

P100 or P121...P123.

See 3.2.3 and P120.

f.bf

Personality fault

Drive Hardware

• Cycle Power

• Power down and install EPM

with valid data

• Reset the drive back to defaults

(P199 = 3, 4) and then re-

program

• If problem persists, contact

factory technical support

f.CF

Control fault

An EPM has been installed that is

either blank or corrupted

f.cF

Incompatible EPM fault An EPM has been installed

that contains data from an

incompatible parameter version

f.dbF

Dynamic Braking fault

Dynamic braking resistors are

overheating

• Increase active decel time

(P105, P126, P127).

• Check mains voltage and P107

f.EF

External fault

• P121…P123 = 21 and that

digital input has been opened.

• P121…P123 = 22 and that

digital input has been closed.

• Correct the external fault

condition

• Make sure digital input is set

properly for NC or NO circuit

f.F1

EPM fault

EPM missing or defective

Power down and replace EPM

f.F2

f.F12

Internal faults

Contact factory technical support

f.Fnr

Control Configuration

Fault

The drive is setup for REMOTE

KEYPAD control (P100=2 or 5) but

is not setup to communicate with

a remote keypad

Set P400 = 1, or P600 = 1

The drive is setup for NETWORK

ONLY control (P100=3) but is not

setup for network communications

Set P400 or P600 to a valid

network communications protocol

selection

f.FoL

Loss of 4-20 mA signal

fault

4-20 mA signal (at TB-25) is below

2 mA (P163 = 1)

Check signal/signal wire

f.GF

OEM Defaults data fault Drive is powered up with

P199 =1 and OEM settings in the

EPM are not valid.

Install an EPM containing valid

OEM Defaults data or change

P199 to 0.

(1)

The drive can only be restarted if the error message has been resent.