Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P101

Standard

Reference

Source

0

0 Keypad (Local or Remote)

Selects the default speed or torque

reference when no Auto Reference is

selected using the TB-13 inputs

1 0-10 VDC
2 4-20 mA
3 Preset #1
4 Preset #2
5 Preset #3
6 Network
7 Preset Sequence Segment #1 Selections 7, 8 & 9 are not valid for

PID setpoint or torque reference.

8 Preset Sequence Segment #2
9 Preset Sequence Segment #3

P102

Minimum

Frequency

0.0

0.0

{Hz} P103

• P102, P103 are active for all speed

references

• When using an analog speed

reference, also see P160, P161

P103

Maximum

Frequency

60.0 7.5

{Hz}

500

Note

• P103 cannot be set below Minimum Frequency (P102)

• To set P103 above 120 Hz:

- Scroll up to 120 Hz; display shows

HiFr

(flashing).

- Release s button and wait one second

- Press s button again to continue increasing P103

WARNING!

Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the

motor/machine may cause damage to equipment and injury to personnel!

P104

Acceleration

Time 1

20.0 0.0 {s} 3600

• P104 = time of frequency change

from 0 Hz to P167 (base frequency)

• P105 = time of frequency change

from P167 to 0 Hz

• For S-ramp accel/decel, adjust

P105

Deceleration

Time 1

20.0 0.0 {s} 3600

Example: if P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz;

rate of frequency change from 0 Hz to 120 Hz = 40.0 s

P106

S-Ramp

Integration Time

0.0

0.0 {s} 50.0

• P106 = 0.0: Linear accel/decel

ramp

• P106 > 0.0: Adjusts S-ramp curve

for smoother ramp

P107

(1)

Line Voltage

Selection

1*

0 Low (120, 200, 400, 480VAC) * The default setting is 1 for all

drives except when using “reset

50” (Parameter P199, selection 4)

with 480V models. In this case, the

default setting is 0.

1 High (120, 240, 480, 600VAC)

(1) Any changes to this parameter will not take effect until the drive is stopped