Commissioning

4.5.3

Advanced Setup Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P160

Speed at

Minimum Signal

0.0

-999.0

{Hz}

1000

f

P161

P160

ref

10V

(20mA)

0V

(4mA)

V0111

P161

Speed at

Maximum Signal

60.0 -999.0

{Hz}

1000

Note

• P160 sets the output frequency at 0% analog input

• P161 sets the output frequency at 100% analog input

• P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate

opposite direction!

• P160 > P161: Drive will react inversely to analog input signal

P162

Analog Input

Filter

0.01 0.00 {s} 10.00

Adjusts the filter on the analog inputs

(TB-5 and TB-25) to reduce the effect

of signal noise

P163

TB-25 Loss

Action

0

0 No Action

• Selects the reaction to a loss of the

4-20 mA signal at TB-25.

• Signal is considered lost if it falls

below 2 mA

• Digital outputs can also indicate a

loss of 4-20 mA signal; see P140,

P142

1 Fault

F.FoL

2 Go to Preset when TB-25 is:

Speed reference: P137

PID feedback source: P137

PID setpoint reference: P233

Torque reference: P333

P164

TB-25 (4-20mA)

Analog Input

Monitoring Level

2.0

0.0 {mA} 10.0

P165

Base Voltage

15 {V} 1000

Valid for V/Hz mode only.

Set voltage for bus compensation in

V/Hz mode

P166

Carrier

Frequency

1

0 4 kHz

• As carrier frequency is increased,

motor noise is decreased

• Observe derating in Section 2.2

• Automatic shift to 4 kHz at 120%

load

1 6 kHz
2 8 kHz
3 10 kHz