Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P197

Clear Fault

History

0

0 No Action
1 Clear Fault History

P199

Program

Selection

0 Operate from User settings
1 Operate from OEM settings

See Notes 1, 2 and 3

2 Reset to OEM default

settings

See Note 1

3 Reset to 60 Hz default

settings

• See Note 4

• Parameters are reset to the

defaults listed in this manual.

• For P199=4, the following

exceptions apply:

- P103, P152, P161, P167 = 50.0 Hz

- P304 = 50 Hz;

- P305 = 1450 RPM

- P107 = 0 (480 V drives only)

4 Reset to 50 Hz default

settings

5 Translate

See Note 5

WARNING!

Modification of P199 can affect drive functionality! STOP and EXTERNAL

FAULT circuitry may be disabled! Check P100 and P121...P123
Note 1

If the EPM does not contain valid OEM settings, a flashing GF will be

displayed when P199 is set to 1 or 2.

Note 2

When P199 is set to 1, the drive operates from the OEM settings stored

in the EPM Module and no other parameters can be changed (

GE

will

be displayed if attempted).

Note 3

Auto Calibration is not possible when operating from OEM Settings.

Note 4

Reset 60 and Reset 50 will set the Assertion Level (P120) to “2” (High).

P120 may need to be reset for the digital input devices being used.

An

F.AL

fault may occur if P120 and the Assertion switch are not set

identically.

Note 5

If an EPM that contains data from a previous compatible software

version is installed:

• The drive will operate according to the previous data, but parameters

cannot be changed (

cE

will be displayed if attempted)

• To update the EPM to the current software version, set P199 = 5. The

parameters can now be changed but the EPM is incompatible with

previous software revisions.