Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P154

TB-30 Scaling:

Torque

100 10

{%} 1000

If P150 = 5 or 6, sets the Torque (as

a percent of motor rated torque) at

which output equals 10 VDC

P155

TB-30 Scaling:

Power (kW)

1.0

0.1

{kW} 200.0

If P150 = 7 or 8, sets the power at

which output equals 10 VDC

P156

Analog Inputs

Configuration

0 TB5: (0 - 10 VDC);

TB25: (4-20mA)
1 TB5: (0 - 5 VDC);

TB25: (4-20mA)
2 TB5: (2 - 10 VDC);

TB25: (4-20mA)
3 TB5: (-10 - +10 VDC);

TB25: (4-20mA)

Available on special option module only

4 TB5: (0 - 10 VDC);

TB25: (0-20mA)
5 TB5: (0 - 5 VDC);

TB25: (0-20mA)
6 TB5: (2 - 10 VDC);

TB25: (0-20mA)
7 TB5: (-10 - +10 VDC);

TB25: (0-20mA)

Available on special option module only

P157

TB5 (0 - 10

VDC) Analog

Input Monitoring

Action

0 No Action

Selects the reaction to a loss of the

0-10 V signal at TB5

1 P157 < P158 - Trip Fault F_FAU
2 P157 < P158 - Run Preset #8
3 P157< P158 - Run Preset

Seq. #16

Minimum time above/below

Monitoring Level (P158) before

triggering action is 500ms.

4 P157 > P158 - Trip Fault F_FAU
5 P157 > P158 - Run Preset *8
6 P157 > P158 - Run Preset

Seq. #16

P158

TB5 (0-10V)

Analog Input

Monitoring Level

(ML)

0.0

-10.0 {VDC} 10.0

P159

0-10V Analog

Input Deadband

0.0

0 {VDC} 10.0

Not active if [-10 to +10 VDC] option

is selected.