Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 44

Advertising
background image

43

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P399

Motor Auto-

calibration

0

0 Calibration Not Done

• If P300 = 4 or 5, motor calibration

must be performed if P399 is not set

to 3 (bypass calibration).

• If P300=2 or 3, motor calibration is

recommended.

• Use option 2 if option 1 failed or in

case of nonstandard motors

• An alternating CAL / Err

will occur

if:

- attempt motor calibration with

P300 = 0 or 1

- motor calibration is attempted

before programming motor data

1 Standard Calibration Enabled

2 Advanced Calibration Enabled

3 Bypass Calibration, enable

operation in vector mode w/o

Auto Calibration

4 Standard Calibration Complete

5 Advanced Calibration

Complete

Note

To run the Auto Calibration:

- Set P302...P306 according to motor nameplate

- Set P399 = 1

- Make sure motor is cold (20° - 25° C)

- Apply a Start command

- Display will indicate

CAL

for about 40 seconds

- Once the calibration is complete, the display will indicate

StoP

;

apply another Start command to actually start the motor

- Parameter P399 will now be set to 2.

(1)

Any changes to this parameter will not take effect until the drive is stopped

(2)

Parameter applicable to models 15HP (11kW) and higher.