Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 41

Advertising
background image

40

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P244

Sleep Entry

Mode

0

0 Enter SLEEP if Drive Speed

<P240

For time longer than P241

1 Enter SLEEP if Feedback

>P243

For time longer than P241 or same

as Sel 0

2 Enter SLEEP if Feedback

<P243

For time longer than P241 or same

as Sel 0

P245

Sleep Entry Stop

Type

0

0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings

P246

Feedback

Recovery

from Sleep

Threshold

0.0

P204 P205

Active only when P247 = 1 or 2

P247

Sleep Recovery

Mode

0

0 Recovery if Speed Setpoint

> P240 or if PID feedback

differs from setpoint by more

than P242
1 Recovery only if Feedback

< P246
2 Recovery only if Feedback

> P246

P250

Auto Rinse in

Sleep

Mode

0

0 Disabled

Activated in sleep mode only.

1 Enabled

Sleep Recovery cancels Auto Rinse

P251

Time Delay

between

Auto Rinses

30.0 0.0 {min} 6553.5

Time delay reset by re/entering sleep

mode

P252

Auto Rinse

Speed

0.0

-500.0 {Hz} 500.0

If P112 = 1, negative sign = reverse

direction

P253

Auto Rinse Time

0.0

0.0 {sec} 6553.5

Does not include time to decel back

to speed

Auto Pump Rinse Setup:

P250=1 (Enabled)

P251=# minutes between each

Pump Rinse

P252=Hz speed of Pump Rinse

P253=# seconds Pump Rinse