Commissioning

NOTE

If the keypad is selected as the auto reference (P121…P124 is 6) and the

corresponding TB-13 input is closed, the AUTO LED and s t LEDs will both be on.

FUNCTIONS THAT FOLLOW ARE APPLICABLE TO SM2 DRIVES 15HP (11kW) AND GREATER

CTRL

CTRL
The CTRL pushbutton selects the start and speed reference control sources for the drive.

Press [

] mode button to accept the new control mode selection.

CTRL LEDs

START CONTROL

REFERENCE CONTROL

REMOTE

LOCAL

MAN
AUTO

[LOCAL] [MAN]

Keypad

P101 Settings

REMOTE

LOCAL

MAN
AUTO

[LOCAL] [AUTO]

Keypad

Terminal 13x Settings

REMOTE

LOCAL

MAN
AUTO

[REMOTE] [MAN]

Terminal Strip

P101 Settings

REMOTE

LOCAL

MAN
AUTO

[REMOTE] [AUTO]

Terminal Strip

Terminal 13x Settings

If P100 = 6 the CTRL button is used to toggle

start control between the terminal strip

[REMOTE] and the keypad [LOCAL]

- REM/LOC LED indicating the present start control source

is ON

- Press [CTRL]; the LED for other start control source will

blink

- Press [M] within 4 sec to confirm the change

- Blinking LED will turn ON (the other LED will turn OFF)

If P113 = 1 the CTRL button is used to toggle

reference control between the TB-13x setup

[AUTO] and P101 [MANUAL]

- AUT/MAN LED indicating present reference control is ON

- Press [CTRL]; the other reference control will blink

- Press [M] within 4 sec to confirm change

- Blinking LED will turn ON (the other LED will turn OFF)

If P100 = 6 and P113 = 1, it is possible to

change the start and reference control sources

at the same time