Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 25

Advertising
background image

24

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P108

Motor Overload

100 30

{%} 100

P109

Motor Overload

Type

0

0 Speed Compensation

Ir

100%

60%

30 f

1

0

V0108

1 No Speed Compensation

P110

Start Method

0

0 Normal
1 Start on Power-up

Drive will automatically start when

power is applied.

2 Start with DC Brake

When start command is applied, drive

will apply DC braking according to

P174, P175 prior to starting the motor

3 Auto Restart

Drive will automatically restart after

faults, or when power is applied.

4 Auto Restart with DC Brake

Combines settings 2 and 3

5 Flying Start/Restart #1

• Drive will automatically restart after

faults, or when power is applied.

• After 3 failed attempts, drive will

Auto Restart with DC brake.

• P110 = 5: Performs speed search,

starting at Max Frequency (P103)

• P110 = 6: Performs speed search,

starting at the last output frequency

prior to faulting or power loss

• If P111 = 0, a flying START is

performed when a start command

is applied.

6 Flying Start/Restart #2

motor current rating

P108 = SM2 output rating x 100

Example: motor = 3 amps; SM2 = 4

amps; P108 = 75%

Note

Do not set above the rated motor current as listed on the motor

dataplate. The motor thermal overload function of the SM2 is UL

approved as a motor protection device. If line power is cycled, the

motor thermal state is reset to cold state. Cycling power after an

overload fault could result in significantly reducing the motor life.