Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P207

Proportional

Gain

5.0

0.0 {%} 100.0

Used to tune the PID loop:

• Increase P207 until system

becomes unstable, then decrease

P207 by 10-15%

• Next, increase P208 until feedback

matches setpoint

• If required, increase P209 to

compensate for sudden changes in

feedback

P208

Integral Gain

0.0

0.0 {s} 20.0

P209

Derivative Gain

0.0

0.0 {s} 20.0

Note

• Derivative Gain is very sensitive to noise on the feedback signal and

must be used with care

• Derivative Gain is not normally required in pump and fan applications

P210

PID Setpoint

Ramp

20.0 0.0 {s} 100.0

• time of setpoint change from P204

to P205 or vice versa.

• Used to smooth the transition

from one PID setpoint to another,

such as when using the Preset PID

Setpoints

(P231...P233)

P214

Minimum Alarm

0.0

P204 P205

Use with P140, P142 = 18...23

P215

Maximum Alarm

0.0

P204 P205

P231

Preset PID

Setpoint #1

0.0

P204 P205

TB-13A activated; P121 = 3 and

P200 = 1 or 2

P232

Preset PID

Setpoint #2

0.0

P204 P205

TB-13B activated; P122 = 3 and

P200 = 1 or 2

P233

Preset PID

Setpoint #3

0.0

P204 P205

TB-13C activated; P123 = 3 and

P200 = 1 or 2

P234

(2)

Preset PID

Setpoint #4

0.0

P204 P205

TB-13D activated; P124 = 3 and

P200 = 1 or 2

P240

Sleep Threshold

0.0

0.0

{Hz} 500.0

• If drive speed < P240 for longer

than P241, output frequency = 0.0

Hz; drive display =

SLP

• P240 = 0.0: Sleep mode is

disabled.

• P200 = 0…2: Drive will start again

when speed command is above

P240

• P242 > 0.0: Drive will restart when

the PID feedback differs from the

setpoint by more than the value

of P242 or when the PID loop

requires a speed above P240.

P241

Sleep Delay

30.0 0.0 {s} 300.0

P242

Sleep Bandwidth

0.0

0.0 B

max

Where: B

max

= |(P205 - P204)|

P243

Feedback Sleep

Entry Threshold

0.0

P204 P205

Active only when P244 = 1 or 2

(2)

Parameter applicable to models 15HP (11kW) and higher.