Commissioning, 4 pid parameters – LEESON SM4 Series Flux Vector User Manual

Page 39

Advertising
background image

38

Commissioning

4.5.4

PID Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P200

PID Mode

0

0 Disabled

• Normal-acting: As feedback

increases, motor speed decreases

• Reverse-acting: As feedback

increases, motor speed increases

• PID mode is disabled in Vector

Torque mode (P300 = 5)

• Selections 3, 4: If P112=1, PID

controller output sets the speed,

(range -max freq to +max freq)

1 Normal-acting

2 Reverse-acting

3 Normal-acting, Bi-directional

4 Reverse-acting, Bi-directional

Note

To activate PID mode, one of the TB-13 inputs (P121...P123) must

be used to select the Auto Reference that matches the desired PID

setpoint reference. If the selected PID setpoint reference uses the same

analog signal as the PID feedback (P201), an

F.IL

fault will occur.

Example: The desired PID setpoint reference is the keypad (s and t).

Set TB-13x = 6 (Auto Reference: Keypad):

• TB-13x = closed: PID mode is active

• TB-13x = open: PID mode is disabled and the drive speed will be

controlled by the reference selected in P101.

P201

PID Feedback

Source

0

0 4-20 mA (TB-25)

Must be set to match the PID

feedback signal

1 0-10 VDC (TB-5)

P202

PID Decimal

Point

1

0 PID Display = XXXX

Applies to P204, P205, P214, P215,

P231...P233, P242, P522, P523

1 PID Display = XXX.X
2 PID Display = XX.XX
3 PID Display = X.XXX
4 PID Display = .XXXX

P203

(2)

PID Units

0

0 %

Select the UNITS LED that will be

illuminated when the drive is running

in PID control mode

1 /UNITS
2 AMPS
3 NONE

P204

Feedback at

Minimum Signal

0.0

-99.9

3100.0 Set to match the range of the

feedback signal being used

Example: Feedback signal is 0 - 300

PSI; P204 = 0.0, P205 = 300.0

P205

Feedback at

Maximum Signal

100.0 -99.9

3100.0

(2)

Parameter applicable to models 15HP (11kW) and higher.