Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

Note

• P110 = 0, 2: Start command must be applied at least 2 seconds

after power-up;

F.UF

fault will occur if start command is applied too

soon.

• P110 = 1, 3…6: For automatic start/restart, the start source must be

the terminal strip and the start command must be present.

• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.

• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail,

drive displays

LC

(fault lockout) and requires manual reset.

• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip

into

F

.

rF

fault.

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to personnel!

Automatic starting/restarting should only be used on equipment that is inaccessible to personnel.

P111

Stop Method

0

0 Coast

Drive’s output will shut off

immediately upon a stop command,

allowing the motor to coast to a stop

1 Coast with DC Brake

The drive’s output will shut off and

then the DC Brake will activate (see

P174, P175)

2 Ramp

The drive will ramp the motor to a

stop according to P105 or P126.

3 Ramp with DC Brake

The drive will ramp the motor to 0 Hz

and then the DC Brake will activate

(see P174, P175)

P112

Rotation

0

0 Forward Only

If PID mode is enabled, reverse

direction is disabled (except for Jog).

1 Forward and Reverse