Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P626

Network Timeout

Action

4

0 No action

Modbus

1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.nF1

0

0 No action

Lecom

1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1

P627

Network Messages

Received

Read-Only: 0 - 9999

Valid network messages received

NOTE: When the number of messages exceeds 9999, the counter resets

and resumes counting from 0.

4.5.9

Sequencer Parameters

The P700 sequencer parameters are listed herein. Refer to section 4.5.7 for P56x Sequencer Diagnostic

Parameters.

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P700

Sequencer

Mode

0

0 Disabled

If P700 = 0 and no reference (P121,

P101) points to any of the sequence

segments, then P701-P799 will not

be displayed on the local keypad.

1 Enabled: transition on timer only
2 Enabled: transition on rising

edge (P121, 122, 123 = 25 step

sequence)

3 Enabled: transition on timer or

rising edge

P701

Sequencer:

TB13A Trigger

Segment

1

1 - 16

TB13A = lowest priority

Asserting TB13A with selection

#24 (Start Sequence), starts the

sequence operation from the

segment specified in this parameter.

P702

Sequencer:

TB13B

Trigger Segment

1

1 - 16

TB13B: higher priority than TB13A

Asserting TB13B with selection

#24 (Start Sequence), starts the

sequence operation from the

segment specified in this parameter.

P703

Sequencer:

TB13C

Trigger Segment

1

1 - 16

TB13C: higher priority thanTB13B, A

Asserting TB13C with selection

#24 (Start Sequence), starts the

sequence operation from the

segment specified in this parameter.

P704

(2)

Sequencer:

TB13D

Trigger Segment

1

1 - 16

TB13D: higher priority than TB13C,

B, A

Asserting TB13D with selection

#24 (Start Sequence), starts the

sequence operation from the

segment specified in this parameter.

(2)

Parameter applicable to models 15HP (11kW) and higher.