Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 58

Advertising
background image

57

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P793

End Segment:

Digital Output

State

Bit0 Relay

bit = 0: OFF (De-energized)

bit = 1: ON (Energized)

The corresponding digital output/

relay must be set to accept value the

from the sequencer: P140, P142=27

Bit1 TB14

P794

End Segment:

TB30 Analog

Output Value

0.00

0.00

{VDC} 10.00

TB30 configuration parameter must

be set to accept this value: P150

= 10

P795

End Segment:

Drive Action

0

0 Keep Running

Recovery: Toggling the START

SEQUENCE will start the cycle

from ‘end segment Stop’ or ‘end

segment DC Brake’.

1 Stop (based on P111)
2 Coast to Stop
3 Quick Stop
4 Coast with DC Brake
5 Ramp with DC Brake
WARNING!

If P795 = 0 then toggling the start sequence input will also restart the

sequencer cycle but in the interim where TB13X is open the drive will

ramp to the standard or specified alternate speed source depending on

the drive configuration.

WARNING

If the input defined to “Start Sequence” is opened during a sequence, the

drive will exit sequencer mode and will run at the specified standard or

alternate speed source (dependent on drive configuration).