Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 35

Advertising
background image

34

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P167

(1)

Base Frequency

60.0 10.0 {Hz} 1500

V0112

P168

Fixed Boost

0.0 {%} 30.0

Note

• P167 = rated motor frequency for standard applications

• P168 default setting depends on drive rating

P169

Accel Boost

0.0

0.0 {%} 20.0

Accel Boost is only active during

acceleration

P170

Slip

Compensation

0.0

0.0 {%} 10.0

Increase P170 until the motor speed

no longer changes between no load

and full load conditions.

P171

(1)

Current Limit

200 30

{%} CLim

max

• When the limit is reached, the

drive displays

CL

, and either the

acceleration time increases or the

output frequency decreases.

• Digital outputs can also indicate

when the limit is reached; see

P140, P142.

• Refer to section 2.2 for CLim

max

P172

Current Limit

Reduction

0

0 Current Limit Reduction

Active - Normal response

In field weakening, the Current Limit

is inversely proportional to the speed.

1 Current Limit Reduction Active

- Fast response
2 Current Limit Reduction

Disabled - Normal response
3 Current Limit Reduction

Disabled - Fast response

P173

Decel Override

Time

2.0

0.0 {s} 60.0

Maximum time before drive trips into

HF fault.

P174

DC Brake

Voltage

0.0

0.0 {%} 30.0

Setting is a percent of the nominal

DC bus voltage.

(1)

The drive can only be restarted if the error message has been reset