Commissioning, 4 commissioning, 1 local keypad & display – LEESON SM4 Series Flux Vector User Manual

Page 18: 15hp (1kw) and greater models

Advertising
background image

17

Commissioning

Control Terminal Strip for 15HP (11 kW) and Greater Drives:

6 25 4 11 13A13B 13C

TXA

5

1 2

14 30 2

AOUT

DIGOUT

2k … 10k

+10

V

+12

V

AIN

AIN

COM

COM

ALsw

17

16

TXB

13D

13D

13D

25

2

4 … 20 mA

5

2

0 … 10 V

1 2 4 13A 13B 13C

+12 VDC - 0 %

. . .

+30 VDC + 0 %

ALsw

+15V

1 2 4 13A 13B 13C

ALsw

COM

4.5 lb-in

(0.5 Nm)

0.25 in (6 mm)

AWG 26…16

(<1mm²)

The digital inputs can be configured for active-high or active-low by setting the Assertion Level

Switch (ALsw) and P120. If wiring to the drive inputs with dry contacts or with PNP solid state

switches, set the switch and P120 to “High” (+). If using NPN devices for inputs, set both to

“Low” (-). Active-high (+) is the default setting.

HIGH = +12 … +30 V

LOW = 0 … +3 V

Note

An F.AL fault will occur if the Assertion Level switch (ALsw) position does not match

the parameter P120 setting and P100 or any of the digital inputs (P121...P123) is set

to a value other than 0.

4 Commissioning

4.1

Local Keypad & Display

FWD

AUTO

REV

STOP

RUN

V0105

15HP (1kW) and greater Models