Installation, 3 control terminals – LEESON SM4 Series Flux Vector User Manual

Page 17

Advertising
background image

16

Installation

Observe the following when using Ground Fault Circuit Interrupters (GFCIs):
• Installation of GFCI only between supplying mains and controller.

• The GFCI can be activated by:

- capacitive leakage currents between the cable screens during operation (especially with long,

screened motor cables)

- connecting several controllers to the mains at the same time

- RFI filters

3.2.3

Control terminals

Control Terminal Strip for 0.33-10HP (0.25-7.5 kW):

6 25 4 11 13A13B13C

17

5

1 2

14 30 16

AOUT

DIGOUT

2k … 10k

+10

V

AIN

AIN

COM

COM

ALsw

25

2

4 … 20 mA

5

2

0 … 10 V

0 … 5 V

1 2 4 13A 13B 13C

+12 VDC - 0 %

+30 VDC + 0 %

ALsw

+15V

1 2 4 13A 13B 13C

ALsw

COM

PNP

NPN

4.5 lb-in

(0.5 Nm)

0.25 in (6 mm)

AWG 26…16

(<1mm²)

V0109

Terminal Data for control connections

1

Digital Input: Start/Stop

input resistance = 4.3kΩ

2

Analog Common

5

Analog Input: 0...10 VDC

input resistance: >50 kΩ

6

Internal DC supply for speed pot

+10 VDC, max. 10 mA

25

Analog Input: 4...20 mA

input resistance: 250Ω

4

Digital Reference/Common

+15 VDC / 0 VDC, depending on assertion level

11

Internal DC supply for external devices

+12 VDC, max. 50 mA

13A

Digital Input: Configurable with P121

input resistance = 4.3kΩ

13B

Digital Input: Configurable with P122

13C

Digital Input: Configurable with P123

13D*

Digital Input: Configurable with P124

14

Digital Output: Configurable with P142

DC 24 V / 50 mA; NPN

30

Analog Output: Configurable with P150…P155 0…10 VDC, max. 20 mA

16

Relay output: Configurable with P140

AC 250 V / 3 A

DC 24 V / 2 A … 240 V / 0.22 A, non-inductive

17

2*

Analog Common

TXA*

RS485 TXA

TXB*

RS485 TXB

* = Terminal is part of the terminal strip for the 15-25 HP models only