Commissioning, 5 vector parameters – LEESON SM4 Series Flux Vector User Manual

Page 42

Advertising
background image

41

Commissioning

4.5.5

Vector Parameters

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P300

(1)

Drive Mode

0

0 Constant V/Hz

Constant torque V/Hz control for

general applications

1 Variable V/Hz

Variable torque V/Hz control for

centrifugal pump and fan applications

2 Enhanced Constant V/Hz

For single or multiple motor

applications that require better

performance than settings 0 or 1,

but cannot use Vector mode, due to:

• Missing required motor data

• Vector mode causing unstable

motor operation

3 Enhanced Variable V/Hz

4 Vector Speed

For single-motor applications

requiring higher starting torque and

speed regulation

5 Vector Torque

For single-motor applications

requiring torque control

independent of speed

Note

To configure the drive for either Vector mode or Enhanced V/Hz mode:

• P300 = 4, 5:

- Set P302...P306 according to motor nameplate

- Set P399 = 1

- Make sure motor is cold (20° - 25° C) and apply a Start command

- Display will indicate

CAL

for about 40 seconds

- Once the calibration is complete, the display will indicate

StoP

; apply

another Start command to actually start the motor

- If an attempt is made to start the drive in Vector or Enhanced V/Hz

mode before performing the Motor Calibration, the drive will display

F.n1d

and will not operate

• P300 = 2, 3: Same as above but only need to set P302…P304

P302

(1

)

Motor Rated

Voltage

0

{V} 600

• Default setting = drive rating

• Set to motor nameplate data

P303

(1)

Motor Rated

Current

0.0 {A} 500.0

P304

(

1)

Motor Rated

Frequency

60

0

{Hz} 1000

Set to motor nameplate data

P305

(1

)

Motor Rated

Speed

1750 300

{RPM} 65000

P306

(1)

Motor Cosine Phi 0.80 0.40 0.99

Note

If motor cosine phi is not known, use one of the following formulas:

cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732)

cos phi = cos [ sin

-1

(magnetizing current / motor current) ]

(1)

The drive can only be restarted if the error message has been reset