Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P718

Segment #2

Digital Output

State

0

Bit0 Relay

bit = 0: OFF (De-energized)

bit = 1: ON (Energized)

The corresponding digital output/

relay must be set to accept value the

from the sequencer: P140, P142=27

Bit1 TB14

P719

Segment #2

TB30

Analog Output

Value

0.00

0.00

{VDC} 10.00

TB30 configuration parameter must

be set to accept this value: P150

= 10

Segment #3

P720

Segment #3

Frequency

Setpoint

0.0

-500.0

{Hz}

500.0

If P112 = 1, negative sign forces

reverse direction

P721

Segment #3

Accel/Decel Time

20.0

0.0

{sec} 3600.0

P722

Segment #3

Time in current

step

0.0

0

0.0

{P708}

6553.5

0

{P708}

65535

Scaling/units depend on P708

Skip segment if time = 0

P723

Segment #3

Digital Output

State

0

Bit0 Relay

bit = 0: OFF (De-energized)

bit = 1: ON (Energized)

The corresponding digital output/

relay must be set to accept value the

Bit1 TB14

P724

Segment #3

TB30

Analog Output

Value

0.00

0.00

{VDC} 10.00

TB30 configuration parameter must

be set to accept this value: P150

= 10

Segment #4

P725

Segment #4

Frequency

Setpoint

0.0

-500.0

{Hz}

500.0

If P112 = 1, negative sign forces

reverse direction

P726

Segment #4

Accel/Decel Time

20.0

0.0

{sec} 3600.0

P727

Segment #4

Time in current

step

0.0

0

0.0

{P708}

6553.5

0

{P708}

65535

Scaling/units depend on P708

Skip segment if time = 0

P728

Segment #4

Digital Output

State

0

Bit0 Relay

bit = 0: OFF (De-energized)

bit = 1: ON (Energized)

The corresponding digital output/

relay must be set to accept value the

Bit1 TB14

P729

Segment #4

TB30

Analog Output

Value

0.00

0.00

{VDC} 10.00

TB30 configuration parameter must

be set to accept this value: P150

= 10