Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 43

Advertising
background image

42

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P310

(1)

Motor Stator

Resistance

0.00 0.00 {Ω} 64.00

• Will be automatically

programmed by P399

• Changing these settings can

adversely affect performance.

Contact factory technical support

prior to changing

P311

(1)

Motor Stator

Inductance

0.0

0.0

{mH} 2000

P315

Dead Time

Compensation

Factor

0.0

-50.0 {%} +50.0 • Adjust dead time correction from

internal default

• Takes effect when P399 = 3.

P330

Torque Limit

100 0

{%} 400

When P300 = 5, sets the maximum

output torque.

P331

Preset Torque

Setpoint #1

100 0

{%} 400

TB-13A activated; P121 = 3 and

P300 = 5

P332

Preset Torque

Setpoint #2

100 0

{%} 400

TB-13B activated; P122 = 3 and

P300 = 5

P333

Preset Torque

Setpoint #3

100 0

{%} 400

TB-13C activated; P123 = 3 and

P300 = 5

P334

(2)

Preset Torque

Setpoint #4

100 0 {%} 400

TB-13D activated; P124 = 3 and

P300 = 5

P340

(1)

Current Loop P

Gain

0.25 0.00 16.0

Changing these settings can

adversely affect performance.

Contact factory technical support

prior to changing.

P341

(1)

Current Loop I

Gain

65

12

{ms} 9990

P342

(1)

Speed Loop

Adjustment

0.0

0.0 {%} 20.0

P343

Slip

Compensation

Response Filter

99

90 {ms} 9999

Low pass filter time constant for

varying the slip compensation

response to changes in the motor

current.

(1)

Any changes to this parameter will not take effect until the drive is stopped

(2)

Parameter applicable to models 15HP (11kW) and higher.