29

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P131

Preset Speed #1

0.0

0.0

{Hz} 500

PRESET

SPEED

13A 13B 13C 13D

1

X

--

--

--

2

--

X

--

--

3

--

--

X

--

4

X

X

--

--

4 (alternate) --

--

--

X

5

X

--

X

--

6

--

X

X

--

7

X

X

X

--

8 (alternate) --

X

--

X

8 (alternate) --

--

X

X

P132

Preset Speed #2

0.0

0.0

{Hz} 500

P133

Preset Speed #3

0.0

0.0

{Hz} 500

P134

Preset Speed #4

0.0

0.0

{Hz} 500

P135

Preset Speed #5

0.0

0.0

{Hz} 500

P136

Preset Speed #6

0.0

0.0

{Hz} 500

P137

Preset Speed #7

0.0

0.0

{Hz} 500

P138

Preset Speed #8

0.0

0.0 {Hz} 500

P140

Relay Output

TB-16, 17

0

0 None

Disables the output

1 Run

Energizes when the drive is running

2 Reverse

Energizes when reverse rotation is

active

3 Fault

De-energizes when the drive trips, or

power is removed

4 Inverse Fault

Energizes when the drive trips

5 Fault Lockout

P110 = 3...6: De-energizes if all

restart attempts fail

6 At Speed

Energizes when output frequency =

commanded frequency

7 Above Preset Speed #6

Energizes when output freq. > P136

8 Current Limit

Energizes when motor current = P171

9 Follower Loss (4-20 mA)

Energizes when 4-20 mA signal falls

below 2 mA

10 Loss of Load

Energizes when motor load drops

below P145; see also P146

• Speed setting is used by P158

• 13D available on 15HP (11kW) &

higher drives.