Troubleshooting and diagnostics, 2 drive configuration messages – LEESON SM4 Series Flux Vector User Manual

Page 64

Advertising
background image

63

Troubleshooting and Diagnostics

5.2

Drive Configuration Messages

When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that

indicates how the drive is configured. If the drive is in a Stop state when this is done, the display

will also indicate which control source commanded the drive to Stop

(the two displays will alternate every second).

Configuration Display

Format = x.y.zz x = Control Source:

L

= Local Keypad

t

= Terminal Strip

r

= Remote Keypad

n

= Network

y = Mode:

S

= Speed mode

P

= PID mode

t

= Vector Torque mode

zz = Reference:

CP

= Keypad s t

EU

= 0-10 VDC (TB-5)

E1

= 4-20 mA (TB-25)

JG

= Jog

nt

= Network

OP

= MOP

P1...P7

= Preset 1...7

01...16

= Sequencer

Segment

Example:

L.S.CP

= Local Keypad Start control, Speed mode, Keypad speed reference

t.p.EU

= Terminal Strip Start control, PID mode, 0-10 VDC setpoint reference

t.C.12

= Terminal Strip Start control, Sequencer Operation (Speed mode),

Segment #12

n.t.p2

= Network Start control, Vector Torque mode, Preset Torque #2 reference

n.S.03

= Network Start control, Speed mode, Speed reference from Sequencer

Segment #03

Stop Source Display

Format = x

.StP

L.stp

= Stop command came from Local Keypad

t.stp

= Stop command came from Terminal Strip

r.stp

= Stop command came from Remote Keypad

n.stp

= Stop command came from Network