Commissioning – LEESON SM4 Series Flux Vector User Manual

Page 28

Advertising
background image

27

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P121

P122

P123

p124

TB-13A Input

Function

TB-13B Input

Function

TB-13C Input

Function

TB-13D* Input

Function

0

0 None

Disables input

1 AUTO Reference: 0-10 VDC

For frequency mode, see P160...P161,

For PID mode, see P204…P205,

For vector torque mode, see P330

2 AUTO Reference: 4-20 mA
3 AUTO Reference: Preset

For frequency mode see P131...P137,

For PID mode, see P231…P233,

For torque mode see, P331…P333

4 AUTO Reference: MOP Up

• Normally open: Close input to

increase or decrease speed, PID

setpoint or torque setpoint.

• MOP Up is not active while in STOP

5 AUTO Reference: MOP Down

6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control Select

Use when P100 = 4, 5 to switch

between terminal strip control and

local or remote keypad control.

9 Network Enable

Required to start the drive through

the network.

10 Reverse Rotation

Open = Forward Closed = Reverse

11 Start Forward

See note for typical circuit

12 Start Reverse
13 Run Forward

See note for typical circuit

14 Run Reverse
15 Jog Forward

Jog Forward speed = P134

16 Jog Reverse

Jog Reverse speed = P135

WARNING! Active even if P112 = 0

17 Accel/Decel #2

See P125, P126

18 DC Brake

See P174; close input to override P175

19 Auxiliary Ramp to Stop

Normally closed: Opening input will

ramp drive to STOP according to P127,

even if P111 is set to Coast (0 or 1).

20 Clear Fault

Close to reset fault

21 External Fault

F

.

EF

Normally closed circuit; open to trip

22 Inverse External Fault

F

.

EF

Normally open circuit; close to trip

23 AUTO Ref: Sequence

Segment #1

Works in Speed Mode only

24 Start Sequence
25 Step Sequence

Transition from non-asserted to

asserted state

26 Suspend Sequence

WARNING!

Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be

deactivated or a fault condition induced.

NOTE: P124

is

applicable to SMV

15HP (11kW) and

greater models

only