C14066

C14067

C14071

Parameter | Name:

C14066 | EPL CN: Max. user data PRes RPDO

Data type: UNSIGNED_16

Index: 10509 = 0x290D

EPL index: See subcodes

The code defines the reserved user data length of the PRes telegrams for Controlled Nodes 1 ... 100. Each subcode

number corresponds to one EPL node with the same node ID. The EPL node must be enabled via code

C14028

.

The subcodes describe the PRes telegrams received. The value must be within the range of 36 ... 1490 bytes.

The values are upper limit values for the entire size of the PDO mappings for received PRes telegrams.

In the configured state, the values stored for the nodes must be identical to the corresponding

C14072

entries.

C14066 must have an identical value in all EPL nodes of the network.
Setting range

(min. value | unit | max. value)

0

Byte

1490

Subcodes

Lenze setting

Info

EPL index

C14066/1

0 byte

EPL CN: max. user data of RPDO

0x1F8D.0x01

...

...

...

...

C14066/100

0 byte

EPL CN: max. user data of RPDO

0x1F8D.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14067 | EPL MN: time-out isochronous comm. CN

Data type: UNSIGNED_32

Index: 10508 = 0x290C

EPL index: See subcodes

The code defines the reserved user data length of the PRes frames for Managing Node, diagnostic device or router.

Each subcode number corresponds to one EPL node with the same node ID. The EPL node must be enabled via code

C14028

.

The subcode describes the PRes telegrams received. The value must be within the limits of 36 ... 1490 bytes.

The values are upper limit values for the entire size of the PDO mappings for received PRes telegrams.

In the configured state, the values stored for the nodes must be identical to the corresponding

C14072

entries.

C14067 must have an identical value in all EPL nodes of the network.
Setting range

(min. value | unit | max. value)

0

ns

4294967295

Subcodes

Lenze setting

Info

EPL index

C14067/1

5000 ns

EPL Time-out isochronous comm.

CN

0x1F92.0x01

...

...

...

...

C14067/100

5000 ns

EPL Time-out isochronous comm.

CN

0x1F92.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14071 | EPL Max. PDO user data RPDO PReq

Data type: UNSIGNED_16

Index: 10504 = 0x2908

EPL index: 0x1F98.0x04

The code defines the maximum data volume to be received by the Controlled Node of the PDP mapping for the PReq

telegram to be defined via one of the codes

C14231

...

C14240

.

In the configured state, the value must be identical to the entry for a response valid for the EPL node.

When a Servo Drive 9400 is used, the code as Managing Node is irrelevant since Servo Drives 9400 as Managing

Nodes only transmit PDO data via broadcast PRes telegrams (C14071 = 36 bytes).
Setting range

(min. value | unit | max. value)

Lenze setting

0

Byte

1490 36 bytes