Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17

80

11

Parameter reference

11.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13062

C13063

Parameter | Name:

C13062 | EPL MN: boot timing

Data type: UNSIGNED_32

Index: 11513 = 0x2CF9

EPL index: See subcodes

The code defines timeouts and waiting times for the booting process of the Managing Node.

• The value "0" for subcode 2, 4, 5 deactivates the time-outs. The Managing Node waits for an indefinite period of

time. No error message is generated.

• The value "0" for subcode 3 deactivates the waiting time. After all expected Controlled Nodes have been detected

by the Managing Node, the Managing Node immediately changes to NMT_MS_PREOPERATIONAL_2.

Observe the following conditions:

• Subcode 1 must be lower than

C13078

- values of all EPL nodes.

• Subcode 3 must be lower than subcode 2.

Setting range

(min. value | unit | max. value)

0

μs

4294967295

Subcodes

Lenze setting

Info

EPL index

C13062/1

2500000 μs

Max. time for detecting a

redundant Managing Node

Waiting time before changing to

NMT_MS_PREOPERATIONAL_1

0x1F89.0x01

C13062/2

60000000 μs

Max. time for device search

Dwell time in

NMT_MS_PREOPERATIONAL_1

Error message if not all

Controlled Nodes are in

NMT_CS_PREOPERATIONAL_1.

0x1F89.0x02

C13062/3

0 μs

Waiting time in

NMT_MS_PREOPERATIONAL_1

0x1F89.0x03

C13062/4

0 μs

Max. time in

NMT_MS_PREOPERATIONAL_2

Error message if not all

Controlled Nodes are in

NMT_CS_PREOPERATIONAL_2.

0x1F89.0x04

C13062/5

0 μs

Max. time in

NMT_MS_READY_TO_OPERATE

Error message if not all

Controlled Nodes are in

NMT_CS_READY_TO_OPERATE.

0x1F89.0x05

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13063 | EPL MN cycle timing

Data type: UNSIGNED_32

Index: 11512 = 0x2CF8

EPL index: See subcodes

The code defines time intervals for the cycle control by the Managing Node.
Setting range

(min. value | unit | max. value)

0

ns

4294967295

Subcodes

Lenze setting

Info

EPL index

C13063/1

2000 ns

Waiting time between SoC and

PReq

0x1F8A.0x01

C13063/2

750000 ns

Time-out SDO communication

0x1F8A.0x02

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT