C14118 | epl mn: link interruptions, C14122 | epl cn response error, C14124 | epl cn response error: monit. thresholds – Lenze E94AYCEP User Manual

Page 116: C14125 | epl mn: break after collisions, C14124, 11 parameter reference

Advertising
background image

11

Parameter reference

11.3

Parameters of the communication module for slot MXI2

117

Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14118

C14122

C14124

C14125

Parameter | Name:

C14118 | EPL MN: Link interruptions

Data type: UNSIGNED_32

Index: 10457 = 0x28D9

EPL index: 0x1C03

The code displays the counter of the Managing Node for interrupted POWERLINK connections. Each event is

counted. Every single event is followed by an error response. A threshold value management is not implemented.
Setting range

(min. value | unit | max. value)

Lenze setting

0

4294967295 0

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14122 | EPL CN response error

Data type: UNSIGNED_32

Index: 10453 = 0x28D5

EPL index: See subcodes

The subcodes of the code indicate Controlled Node-specific cumulative counters for missing PRes frames. The

behaviour corresponds to a node The behaviour corresponds to subcode 1 of the single error counters (

C14116

).

Each subcode corresponds to an EPL node with node ID = subcode number.
Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C14122/1

0

EPL CN response error

0x1C07.0x01

...

...

...

...

C14122/100

0

EPL CN response error

0x1C07.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14124 | EPL CN response error: monit. thresholds

Data type: UNSIGNED_32

Index: 10451 = 0x28D3

EPL index: See subcodes

Setting range

(min. value | unit | max. value)

0

1000

Subcodes

Lenze setting

Info

EPL index

C14124/1

9

EPL CN response error: monit.

thresholds

0x1C09.0x01

...

...

...

...

C14124/100

9

EPL CN response error: monit.

thresholds

0x1C09.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14125 | EPL MN: Break after collisions

Data type: UNSIGNED_32

Index: 10450 = 0x28D2

EPL index: 0x1C12

The code determines the number of EPL cycles for the duration of which the Managing Node interrupts the cycle

sequence after a POWERLINK collision has occurred.
Setting range

(min. value | unit | max. value)

Lenze setting

0

Cycles

100 1 cycles

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Advertising