C13219

C13225

Parameter | Name:

C13219 | EPL device type MN

Data type: UNSIGNED_32

Index: 11356 = 0x2C5C

EPL index: See subcodes

The code contains the device type ID of the declared EPL nodes. Each subcode corresponds to an EPL node with node

ID = subcode number.

When being in the configured status, the values must be identical with the device types stored locally in each EPL

node under

C13030

.

Subcodes

Lenze setting

Info

EPL index

C13219/1

0

Managing Node

0x1F84.0xF0

C13219/2

0

Diagnostics device

0x1F84.0xFD

C13219/3

0

router

0x1F84.0xFE

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13225 | EPL MN: Max. user data RPDO

Data type: UNSIGNED_16

Index: 11350 = 0x2C56

EPL index: See subcodes

The code defines the reserved user data length of the PRes frames. Each subcode number corresponds to an EPL

node with the same node ID.

The subcode describes the PRes frames received. The value must be within the limits of 36 ... 1490 bytes.

The values are upper limit values for the total size of the PDO mappings which must be defined each one of the

codes

C13231

...

C13240

for PRes frames received.

In the configured state, the values stored for the EPL nodes must be identical to the corresponding

C13072

entries.

C13066

must have an identical value in all EPL nodes of the network.

Setting range

(min. value | unit | max. value)

0

Byte

1490

Subcodes

Lenze setting

Info

EPL index

C13225/1

0 byte

Managing Node

0x1F8D.0xF0

C13225/2

0 byte

Diagnostics device

0x1F8D.0xFD

C13225/3

0 byte

router

0x1F8D.0xFE

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT