Epl: internal watchdog activated [0x00c86011, Epl: internal error [0x00c86100, Epl: internal error [0x00c86101 – Lenze E94AYCEP User Manual

Page 62: Epl: invalid pdo mapping detected [0x00c86110, Epl: invalid parameter set [0x00c8641f, Epl: lenze setting loaded [0x00c86420, 0x00c86011, 0x00c86100, 0x00c86101, 0x00c86110

Advertising
background image

10

Error messages

10.1

Error messages of the communication module

63

Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

EPL: Internal watchdog activated [0x00c86011]

EPL: Internal error [0x00c86100]

EPL: Internal error [0x00c86101]

EPL: Invalid PDO mapping detected [0x00c86110]

EPL: Invalid parameter set [0x00c8641f]

EPL: Lenze setting loaded [0x00c86420]

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication module is defective.

Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error.

Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error.

Send communication module together with a

description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The entered PDO mapping is invalid.

Re-execute PDO mapping.

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

No active parameter set could be loaded.

Download application again (including module).

Response (Lenze setting printed in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Access via the Servo Drive 9400 to a parameter set in the

memory module failed.

Download application again (including module).