Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17

82

11

Parameter reference

11.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13072

C13074

C13075

C13078

Parameter | Name:

C13072 | EPL Max. PDO user data TPDO PRes

Data type: UNSIGNED_16

Index: 11503 = 0x2CEF

EPL index: 0x1F98.0x05

The code defines the maximum PDO data size to be sent by the EPL node for the current network configuration. The

PDO mapping

C13531

can assign data with a total size greater than or equal to C13072.

In the configured state, C13072 must be identical to the entry in

C13066

valid for the EPL node.

Setting range

(min. value | unit | max. value)

Lenze setting

0

Byte

1490 400 bytes

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13074 | EPL multi-stage cycle timing

Data type: UNSIGNED_8

Index: 11501 = 0x2CED

EPL index: 0x1F98.0x07

This code serves to define the maximum number of the multiplexed cycles.

If, e.g., the value "3" is entered, the multiplexed cycle is repeated every three cycles. Within one multiplexed cycle,

the nodes are queried according to the values in code

C13079

. If, e.g., the value "2" is entered for a node in

C13079/

x

, it is always queried only in the second cycle of the three multiplexed cycles.

Setting range

(min. value | unit | max. value)

Lenze setting

0

Cycles

255 0 cycles

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13075 | EPL SDO channel width

Data type: UNSIGNED_16

Index: 11500 = 0x2CEC

EPL index: 0x1F98.0x08

The code defines the maximum user data size of asynchronous frames. Protocol-specific headers for POWERLINK,

UDP/IP and others as well as service-specific headers are to be interpreted as part of the user data.

In the configured state, the C13075 values of all EPL nodes must be identical.
Setting range

(min. value | unit | max. value)

Lenze setting

282

Byte

1500 282 bytes

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13078 | EPL CN: Max. time - MN detection

Data type: UNSIGNED_32

Index: 11497 = 0x2CE9

EPL index: 0x1F99

The code defines the time interval needed for detecting a Managing Node. If a booting Controlled Node detects a

Managing Node during the interval, it changes to NMT_CS_PREOPERATIONAL_1. If not, it changes to "Basic

Ethernet Mode".
Setting range

(min. value | unit | max. value)

Lenze setting

0

μs

4294967295 10000000 μs

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT