C13115 | epl mn: frame error (crc), C13116 | epl mn: frame collisions, C13117 | epl mn: cycle time violation – Lenze E94AYCEP User Manual

Page 85: C13115/3, C13117/3, 11 parameter reference

Advertising
background image

Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17

86

11

Parameter reference

11.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13115

C13116

C13117

Parameter | Name:

C13115 | EPL MN: Frame error (CRC)

Data type: UNSIGNED_32

Index: 11460 = 0x2CC4

EPL index: See subcodes

The POWERLINK telegrams of the EPL network are protected by a checksum. The Managing Node counts the

checksum errors which signalise a falsification of the frame.

The monitoring response is determined via

C13891/4

.

Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13115/1

0

CumulativeCnt_U32

0x1C00.0x01

C13115/2

0

ThresholdCnt_U32

0x1C00.0x02

C13115/3

9

Threshold_U32

0x1C00.0x03

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13116 | EPL MN: Frame collisions

Data type: UNSIGNED_32

Index: 11459 = 0x2CC3

EPL index: See subcodes

The code indicates the collision counter of the Managing Node.

The Managing Node detects frame collisions in the EPL segment. This code contains the number of detected

collisions.

Each event is counted. Every single event is followed by an error message. No threshold value management is

implemented.

Due to extended topology options of EPL compared to the standard Ethernet according to IEEE802.3 it is not

mandatory that the Managing Node recognises all collisions that occur in the segment.
Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13116/1

0

CumulativeCnt_U32

0x1C01.0x01

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13117 | EPL MN: Cycle time violation

Data type: UNSIGNED_32

Index: 11458 = 0x2CC2

EPL index: See subcodes

The code indicates the counters of the Managing Node for cycle time overflows.

The monitoring response is determined via

C13891/1

.

Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13117/1

0

CumulativeCnt_U32

0x1C02.0x01

C13117/2

0

ThresholdCnt_U32

0x1C02.0x02

C13117/3

9

Threshold_U32

0x1C02.0x03

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT