C14103 | epl nmt command: enable, C14104 | epl nmt command: command id, C14105 | epl nmt command: target address – Lenze E94AYCEP User Manual

Page 114: C14110 | epl fault memory, 11 parameter reference

Advertising
background image

11

Parameter reference

11.3

Parameters of the communication module for slot MXI2

115

Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14103

C14104

C14105

C14110

Parameter | Name:

C14103 | EPL NMT command: Enable

Data type: UNSIGNED_8

Index: 10472 = 0x28E8

EPL index: 0x1F9F.0x01

The code enables the NMT command defined via

C14104

/

C14105

. The values have the following meaning:

• 0: The command is inhibited.

• 1: The command is enabled.

After the NMT command has been executed, the code is automatically set to FALSE.

NMT commands can cause serious faults in the network. Cycle and monitoring errors can occur.
Setting range

(min. value | unit | max. value)

Lenze setting

0

1 0

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14104 | EPL NMT command: Command ID

Data type: UNSIGNED_8

Index: 10471 = 0x28E7

EPL index: 0x1F9F.0x02

The code defines the command to be executed.

NMT commands can cause serious faults in the network. Cycle and monitoring errors can occur.
Selection list

(Lenze setting printed in bold)

34 StopNode
40 ResetNode
41 ResetCommunication
42 ResetConfiguration

255 No command

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14105 | EPL NMT command: Target address

Data type: UNSIGNED_8

Index: 10470 = 0x28E6

EPL index: 0x1F9F.0x03

The code defines the destination node of the command via its node address. The node address "255" addresses all

EPL nodes of the network. "0" is an invalid address, a command with destination node "0" is ineffective.

NMT commands can cause serious faults in the network. Cycle and monitoring errors can occur.
Setting range

(min. value | unit | max. value)

Lenze setting

0

255 0

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C14110 | EPL fault memory

Data type: INTEGER_8

Index: 10465 = 0x28E1

EPL index: 0x1001

The code indicates the currently pending errors (according to error classes).

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Advertising