C13118

C13122

C13124

C13125

Parameter | Name:

C13118 | EPL MN: Link interruptions

Data type: UNSIGNED_32

Index: 11457 = 0x2CC1

EPL index: 0x1C03

The code displays the counter of the Managing Node for interrupted POWERLINK connections. Each event is

counted. Every single event is followed by an error response. A threshold value management is not implemented.
Setting range

(min. value | unit | max. value)

Lenze setting

0

4294967295 0

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13122 | EPL CN response error

Data type: UNSIGNED_32

Index: 11453 = 0x2CBD

EPL index: See subcodes

The subcodes of the code indicate Controlled Node-specific cumulative counters for missing PRes frames. The

behaviour corresponds to a node The behaviour corresponds to subcode 1 of the single error counters (

C13116

).

Each subcode corresponds to an EPL node with node ID = subcode number.
Setting range

(min. value | unit | max. value)

0

4294967295

Subcodes

Lenze setting

Info

EPL index

C13122/1

0

EPL CN response error

0x1C07.0x01

...

...

...

...

C13122/100

0

EPL CN response error

0x1C07.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13124 | EPL CN response error: monit. thresholds

Data type: UNSIGNED_32

Index: 11451 = 0x2CBB

EPL index: See subcodes

Setting range

(min. value | unit | max. value)

0

1000

Subcodes

Lenze setting

Info

EPL index

C13124/1

9

EPL CN response error: monit.

thresholds

0x1C09.0x01

...

...

...

...

C13124/100

9

EPL CN response error: monit.

thresholds

0x1C09.0x64

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13125 | EPL MN: Break after collisions

Data type: UNSIGNED_32

Index: 11450 = 0x2CBA

EPL index: 0x1C12

The code determines the number of EPL cycles for the duration of which the Managing Node interrupts the cycle

sequence after a POWERLINK collision has occurred.
Setting range

(min. value | unit | max. value)

Lenze setting

0

Cycles

100 1 cycles

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT