1 inputs_can2, 2 outputs_can2, 3 process data telegram – Lenze DDS System bus CAN for PLC User Manual

Page 103: Inputs_can2, Outputs_can2, Process data telegram, System bus (can) for lenze plc devices, Can system blocks

Advertising
background image

System bus (CAN) for Lenze PLC devices

CAN system blocks

7.4

CAN2_IO (node number: 32)

7−15

L

PLC−Systembus EN 2.0

7.4.1

Inputs_CAN2

Variable

Data type

Signal type

Address

Display code

Display

format

Notes

CAN2_nInW1_a

Integer

Analog

%IW32.0

C0866/4

dec [%]

CAN2_nInW2_a

%IW32.1

C0866/5

CAN2_bInB0_b

Bool

Binary

%IX32.0.0

hex

...

...

C0863/3

CAN2_bInB15_b

%IX32.0.15

CAN2_bInB16_b

%IX32.1.0

...

...

C0863/4

CAN2_bInB31_b

%IX32.1.15

CAN2_dnInD1_p

Double integer

Position

%ID32.0

C0867/2

dec [inc]

CAN2_nInW3_a

Integer

Analog

%IW32.2

C0866/6

dec [%]

CAN2_nInW4_a

%IW32.3

C0866/7

7.4.2

Outputs_CAN2

Variable

Data type

Signal type

Address

Display code

Display

format

Notes

CAN2_nOutW1_a

Integer

Analog

%QW32.0

C0868/4

dec [%]

CAN2_nOutW2_a

%QW32.1

C0868/5

CAN2_bFDO0_b

Bool

Binary

%QX32.0.0

C0151/2

hex

Display code in hex
as double word

...

...

CAN2_bFDO15_b

%QX32.0.15

CAN2_bFDO16_b

%QX32.1.0

...

...

CAN2_bFDO31_b

%QX32.1.15

CAN2_dnOutD1_p

Double integer

Position

%QD32.0

C0869/2

dec [inc]

CAN2_nOutW3_a

Integer

Analog

%QW32.2

C0868/6

dec [%]

CAN2_nOutW4_a

%QW32.3

C0868/7

7.4.3

Process data telegram

The process data telegram consists of an identifier and 8 bytes of user data.

11 bit

8 bytes user data

Identifier

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Information on the identifier can be found in chapter 2.4.1.

(

^ 2−3)