7.7

CAN_Synchronization (node number: 102)

System bus (CAN) for Lenze PLC devices

CAN system blocks

7−24

L

PLC−Systembus EN 2.0

Axis synchronisation via terminal

The transmission paths for the sync signal and the process signals are separated.

·

The process signals are applied via a freely selectable input channel (e. g. AIF interface, DF
input).

·

The sync signal is injected via terminal:

PLC

Terminal for sync signal

9300 Servo PLC

X5/E5

Drive PLC

X3/I1

ECSxA

X6/DI1

Note!

For the synchronisation via terminal, in addition to the SB CAN_Synchronization the SB
DIGITAL_IO has to be included in the control configuration of the Drive PLC Developer Studio.

Examples for applications:

·

Specification of cyclic, synchronised position setpoint information for multi−axis applications
via other bus systems (e. g. INTERBUS).

·

Synchronisation of the internal process cycles to higher−level process controls.

Synchronisation time

After mains power−up and the initialisation time of the PLC, an additional period is required for
synchronisation.

The synchronisation time depends on

·

the baud rate of the system bus

·

the starting time (arrival of the first sync telegram/signal)

·

the interval of the sync telegrams/signals

·

the sync correction factor (C0363)

·

the operating mode (C1120)