5 cycle time (canaux2_out/canaux3_out), 6 delay time (canaux2_out/canaux3_out), Cycle time (canaux2_out/canaux3_out) – Lenze DDS System bus CAN for PLC User Manual
Page 80: Delay time (canaux2_out/canaux3_out), System bus (can) for lenze plc devices, Configuration (can−aux interface)
![background image](/manuals/565946/80/background.png)
System bus (CAN) for Lenze PLC devices
Configuration (CAN−AUX interface)
6−6
l
PLC−Systembus EN 2.0
6.5
Cycle time (CANaux2_OUT/CANaux3_OUT)
The transmission of the output data of CANaux2_OUT and CANaux3_OUT can be carried out in an
event−controlled or time−controlled manner.
·
The configuration of the transmission mode is effected via code C2456/x:
Code
LCD
Possible settings
Information
Lenze
Selection
C2456
0
{1}
65000
0 = event−controlled transmission
Factor to the task time for
transmitting the process data
object
2
3
CAN2_OUT T
CAN3_OUT T
0
0
CANaux2_OUT
CANaux3_OUT
Event−controlled transmission
C2456/x = 0
·
The transmission of the output data is always effected if a value has changed within the
8 bytes of user data (Lenze setting).
Time−controlled transmission
C2456/x = 1 ... 65000
·
The transmission of the output data is effected within the cycle time set in C2456/x (relating to
the task cycle time).
Example:
·
The CAN object is used in a 10 ms task.
·
Factor set via C2456/2 = 5
ð
The CAN object is transmitted after every fifth cycle of the task, i. e. every 50 ms (10 ms x 5).
6.6
Delay time (CANaux2_OUT/CANaux3_OUT)
For the transmission of the output data of CANaux2_OUT and CANaux3_OUT a delay time can be
configured via code C2456/4:
Code
LCD
Possible settings
Information
Lenze
Selection
C2456
4 CAN delay
20
0
{1 ms}
65000 Delay time for sending the process
data object