8 reset node, 9 system bus management, Reset node – Lenze DDS System bus CAN for PLC User Manual

Page 68: System bus management, System bus (can) for lenze plc devices

Advertising
background image

System bus (CAN) for Lenze PLC devices

Configuration (FIF interface)

5−8

l

PLC−Systembus EN 2.0

5.8

Reset node

Changes with regard to the CAN baud rate, the node addresses, and the identifiers only are accepted
after a reset node.

A reset node can be effected by

·

Reconnection of the mains

·

Reset node command via NMT command.

(

^ 2−6)

·

Reset node command via the FIF_CAN_Management SB

(

^ 8−4)

·

Reset node via C2458:

Code

LCD

Possible settings

Information

Lenze

Selection

C2458 Reset node

0

0

No function

1

FIF−CAN reset node

FIF−CAN reset node

5.9

System bus management

Via the FIF_CAN_Management SB,

·

a reset node can be activated.

·

"Communication error" and "Bus off state" can be processed in the PLC program.

·

the instant of transmission of FIF−CAN2_OUT and FIF−CAN3_OUT can be influenced.

Tip!

Detailed information on the FIF_CAN_Management SB can be found in chapter 8.4.

(

^ 8−4)