8 reset node, 9 system bus management, Reset node – Lenze DDS System bus CAN for PLC User Manual
Page 68: System bus management, System bus (can) for lenze plc devices
![background image](/manuals/565946/68/background.png)
System bus (CAN) for Lenze PLC devices
Configuration (FIF interface)
5−8
l
PLC−Systembus EN 2.0
5.8
Reset node
Changes with regard to the CAN baud rate, the node addresses, and the identifiers only are accepted
after a reset node.
A reset node can be effected by
·
Reconnection of the mains
·
Reset node command via NMT command.
(
·
Reset node command via the FIF_CAN_Management SB
(
^ 8−4)
·
Reset node via C2458:
Code
LCD
Possible settings
Information
Lenze
Selection
C2458 Reset node
0
0
No function
1
FIF−CAN reset node
FIF−CAN reset node
5.9
System bus management
Via the FIF_CAN_Management SB,
·
a reset node can be activated.
·
"Communication error" and "Bus off state" can be processed in the PLC program.
·
the instant of transmission of FIF−CAN2_OUT and FIF−CAN3_OUT can be influenced.
Tip!
Detailed information on the FIF_CAN_Management SB can be found in chapter 8.4.
(
^ 8−4)