System bus (CAN) for Lenze PLC devices

"CAN" system bus interface configuration

3−3

l

PLC−Systembus EN 2.0

3.3

Node address (node ID)

Assign a node address − also called Node ID − within the range of 1 to 63 to each node within the
system bus network as a definite identification.

·

The same node address may not be assigned more than once within the network.

·

The configuration of the node address for the PLC is carried out via code C0350:

Code

LCD

Possible settings

Information

Lenze

Selection

C0350 CAN address

1

1

{1}

63 System bus − node address

·

Save changes with C0003 = 1.

·

Changes are only valid after
reset node!

Allocation of the node address for the data exchange among Lenze devices

If Lenze devices are provided with node addresses in a consistent ascending order, the identifiers
of the event−controlled data objects (CAN2_IO/CAN3_IO) are set in way by the factory which enables
a communication from one device to the other:

L

Node-ID 1

CAN2_OUT

CAN2_IN

CAN3_OUT

CAN3_IN

L

Node-ID 2

CAN2_OUT

CAN2_IN

CAN3_OUT

CAN3_IN

L

Node-ID 3

Fig. 3−1

Data exchange among Lenze devices