6 l_cangetreloccobid - querying the cob-id range, 6 l_cangetreloccobid − querying the cob−id range, System bus (can) for lenze plc devices – Lenze DDS System bus CAN for PLC User Manual

Page 149: Lenzecandrv.lib function library

Advertising
background image

System bus (CAN) for Lenze PLC devices

LenzeCanDrv.lib function library

10.6

L_CanGetRelocCobId − querying the COB−ID range

10−7

L

PLC−Systembus EN 2.0

10.6

L_CanGetRelocCobId − querying the COB−ID range

Function

INT

L_CanGetRelocCobId (wDrvNr)

By means of this function the starting identifier of the identifier range (COB−ID range) consisting of
64 objects can be determined for reception operations.

·

This function only is relevant for the 9300 Servo PLC!

L_CanGetRelocCobId

wDrvNr

Transfer parameters

Identifier

Data type

Possible settings

Information

wDrvNr

Word

10

System bus

Return value

Data type

Value

Meaning

Priority

Double integer

−121

Incorrect driver number (wDrvNr)

1 (high)

−120

Driver not initialised

2 (low)

* If there are several error causes, always the return value associated with the error cause

of the highest priority is returned.

0

Return value for use in Drive PLC, as function only is relevant for 9300 Servo PLC!

192...319

Start identifier of the free range 1

832...1344

Start identifier of the free range 2

1664...1728

Start identifier of the free range 3

1856...1984

Start identifier of the free range 4

Note!

From version 6.x of the 9300 Servo PLC, all free identifiers are provided.

Example

Calling the function in ST:

g_nRelocCobIdLocation :=

L_CanGetRelocCobId(10);