System bus (CAN) for Lenze PLC devices
Configuration (AIF interface)
4−8
l
PLC−Systembus EN 2.0
4.7
Reset node
Changes with regard to the CAN baud rate, the node addresses, and the identifiers only are accepted
after a reset node.
A reset node can be effected by
·
Reconnection of the mains
·
Reset node command via NMT command.
(
·
Reset node command via the CAN_Management SB
(
·
Reset node via C0358:
Code
LCD
Possible settings
Information
Lenze
Selection
C0358 Reset node
0
0
No function
1
CAN reset node
Reset node
4.8
Monitoring processes
4.8.1
Time monitoring for XCAN1_IN ... XCAN3_IN
For the inputs of the XCAN1_IN ... XCAN3_IN process data objects a time monitoring can be
configured via C2357:
Code
LCD
Possible settings
Information
Lenze
Selection
C2357 CE monit time
0
{1 ms}
65000 Monitoring time for XCAN process
data input objects
1
3000
XCAN1_IN
2
3000
XCAN2_IN
3
3000
XCAN3_IN
4
1
Bus−off
The response for the case that no telegram has been received within the defined monitoring time can
be configured via code C2382/x:
Code
LCD
Possible settings
Information
Lenze
Selection
C2382 XCAN Conf. CE
0
0
Off
1
Controller inhibit
2
Quick stop (QSP)
Configuration of XCAN monitoring
"BusOffState"
·
Controller inhibit or quick stop
(QSP) can only be carried out for
9300 Servo PLC and ECSxA!
1
0
XCAN1_IN
2
0
XCAN2_IN
3
0
XCAN3_IN
4
0
Bus−off
5
0
Live guarding event