System bus (CAN) for Lenze PLC devices
Configuration (AIF interface)
4−5
l
PLC−Systembus EN 2.0
·
Please note that the identifier of the telegram to be transmitted has to comply with the
identifier of the process data input object to be activated.
·
In the case of an individual address allocation, the identifier for the process data objects is
composed as follows:
Identifier + 384 ) value of C2354/x
x = subcode
·
Thus, identifiers in the range of 384 ... 2047 can be allocated for the process data objects.
4.4.2
Display of the identifier set
Via C2355 you can have the identifier displayed which is set for the process data objects.
·
C2355 is a display code, settings cannot be carried out via C2355.
Code
LCD
Possible settings
Information
Lenze
Selection
C2355
1
2
3
4
5
6
XCAN Id
XCAN1_IN Id
XCAN1_OUT Id
XCAN2_IN Id
XCAN2_OUT Id
XCAN3_IN Id
XCAN3_OUT Id
g
384
{1}
2047 System bus identifier
for the process data objects
XCAN1_IN
XCAN1_OUT
XCAN2_IN
XCAN2_OUT
XCAN3_IN
XCAN3_OUT