System bus (can) for lenze plc devices, General information, 2 command code – Lenze DDS System bus CAN for PLC User Manual

Page 24

Advertising
background image

System bus (CAN) for Lenze PLC devices

General information

2−12

l

PLC−Systembus EN 2.0

2.7.1.2

Command code

Identifier

Command

code

Index

Subindex

Data 1

Data 2

Data 3

Data 4

Low byte

High byte

Among other things, the command code contains the command to be carried out as well as
information on the parameter data length, and is structured as follows:

Bit 7 (MSB)

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Command

Command Specifier (cs)

Length

e

s

Write request

0

0

1

0

00 = 4 bytes
01 = 3 bytes
10 = 2 bytes

11 = 1 byte

1

1

Write response

0

1

1

0

0

0

Read request

0

1

0

0

0

0

Read response

0

1

0

0

1

1

Error Response

1

0

0

0

0

0

0

0

Command code for parameters with 1, 2, or 4 bytes data length:

4 byte data

(32 bit)

2 byte data

(16 bit)

1 byte data

(8 bit)

Command

hex

dec

hex

dec

hex

dec

Information

Write Request

23

35

2B

43

2F

47

Send parameter to a node

Write Response

60

96

60

64

60

96

Node response to "write request" (acknowledgement)

Read Request

40

64

40

64

40

64

Request for reading a parameter of a node

Read Response

43

67

4B

75

4F

79

Response to the read request with an actual value

Error Response

80

128

80

128

80

128

Node reports an error with regard to communication

"Error Response" command

In the case of this error, an "Error Response" is generated by the node that is addressed.

·

This telegram in data 4 always contains the value "6", and in data 3 an error code:

Error Response command code

Data 3

Data 4

Error message

80

hex

3

6

Access denied

5

Incorrect subindex

6

Incorrect index

C0

hex

8

Job was not edited
(for 8200 vector + FIF module)