System bus (CAN) for Lenze PLC devices

"CAN" system bus interface configuration

3−6

l

PLC−Systembus EN 2.0

3.5

Cycle time (CAN2_OUT/CAN3_OUT)

The transmission of the output data of CAN2_OUT and CAN3_OUT can be carried out in an
event−controlled or time−controlled manner.

·

The configuration of the transmission mode is effected via code C0356/x:

Code

LCD

Possible settings

Information

Lenze

Selection

C0356

2
3

CAN2_OUT T
CAN3_OUT T

0
0

0

{1}

65000

0 = event−controlled transmission

Factor to the task time for
transmitting the process data
object

Event−controlled transmission

C0356/x = 0

·

The transmission of the output data is always effected if a value has changed within the
8 bytes of user data (Lenze setting).

Time−controlled transmission

C0356/x = 1 ... 65000

·

The transmission of the output data is effected within the cycle time set in C0356/x (relating to
the task cycle time).

Example:

·

The CAN object is used in a 10 ms task.

·

Factor set via C0356/2 = 5

ð

The CAN object is transmitted after every fifth cycle of the task, i. e. every 50 ms (10 ms x 5).

3.6

Delay time (CAN2_OUT/CAN3_OUT)

For the transmission of the output data of CAN2_OUT and CAN3_OUT a delay time can be configured
via code C0356/4:

Code

LCD

Possible settings

Information

Lenze

Selection

C0356

4 CAN delay

20

0

{1 ms}

65000 Delay time for sending the process

data object.

If the NMT state Operational (to Pre−operational or Stopped) is reached, the "CANdelay" delay time
is started. After the delay time has expired, the PDOs CAN−OUT2 and CAN−OUT3 are transmitted
for the first time.