System bus (CAN) for Lenze PLC devices

FIF−CAN system blocks

8.4

FIF_CAN_Management (node number: 111)

8−5

L

PLC−Systembus EN 2.0

8.4.2

FIF_Outputs_CAN_Management

Variable

Data type

Signal type

Address

Display

code

Display

format

Notes

FIF_CAN_bResetNode_b

Bool

Binary

%QX111.0.0

Carry out reset node of the FIF−CAN

FIF_CAN_bTxCan2Synchronized_b

%QX111.0.1

Transmit FIF−CAN2_OUT with sync
telegram.

FIF_CAN_bTxCan3Synchronized_b

%QX111.0.2

Transmit FIF−CAN_OUT with sync
telegram.

Note!

If FIF_CAN_bTxCan2Synchronized_b and/or FIF_CAN_bTxCan3Synchronized_b are integrated, it
is required to configure the device as sync transmitter. The data are transmitted immediately after
the sync telegram is sent.

8.4.3

Activating a reset node

A reset node can be activated by setting FIF_CAN_bResetNode_b to TRUE or C2458 = 1.

Tip!

Even if the FIF_CAN_Management SB has not been assigned to the control configuration, a reset
node can be activated via C2458.

(

^ 5−8)

8.4.4

Defining the instant of transmission for FIF−CAN2_OUT/FIF−CAN3_OUT

Via FIF_CAN_bTxCan2Synchonized_b and FIF_CAN_bTxCan3Synchonized_b you define the
instant of transmission for the CAN objects FIF−CAN2_OUT and FIF−CAN3_OUT:

·

FALSE: Data from FIF−CAN2_OUT/FIF−CAN3_OUT are sent at the end of the process image.

·

TRUE: Data from FIF−CAN2_OUT/FIF−CAN3_OUT are sent to sync.
– The identifiers for the sync transmission and reception telegram can be set via

C2467/C2468.

– The sync Tx time can be set via C2469.