3 bus load by the plc, Bus load by the plc, Pter 3.13.3 – Lenze DDS System bus CAN for PLC User Manual
Page 49: System bus (can) for lenze plc devices, Can" system bus interface configuration
![background image](/manuals/565946/49/background.png)
System bus (CAN) for Lenze PLC devices
"CAN" system bus interface configuration
3−15
l
PLC−Systembus EN 2.0
3.13.3
Bus load by the PLC
Via C0361 you can receive a percentage display of the extent to which the system bus is loaded by
the telegrams of the PLC.
·
Only valid telegrams are considered.
·
Each transmit and receive channel is evaluated separately.
Code
LCD
Possible settings
Information
Lenze
Selection
C0361 Load IN/OUT
g
0
{1 %}
100 System bus − bus load
·
Trouble−free operation demands
that the total bus load (all
connected devices) does not
exceed 80 %.
1 Load OUT
All sent
2 Load IN
All received
3 Load OUT1
Sent on CAN_OUT1
4 Load OUT2
Sent on CAN_OUT2
5 Load OUT3
Sent on CAN_OUT3
6 Load POUT1
Sent on parameter data channel 1
7 Load POUT2
Sent on parameter data channel 2
8 Load IN1
Received from CAN_IN1
9 Load IN2
Received from CAN_IN2
10 Load IN3
Received from CAN_IN3
11 Load PIN1
Received from parameter data
channel 1
12 Load PIN2
Received from parameter data
channel 2
Limits of the data transmission
Data transmission is limited by the number of telegrams per time unit and by the data transmission
speed.
·
For a data exchange within a drive system only consisting of Lenze controllers/PLCs, these
limits can be determined by adding code C0361/1 of all devices involved.
·
Example: Three controllers are connected to each other via the system bus:
Value of C0361/1 on controller 1:
23.5 % bus load
Value of C0361/1 on controller 2:
12.6 % bus load
Value of C0361/1 on controller 3:
16.0 % bus load
52.1 % total bus load
Tip!
·
The bus load of all devices involved should not exceed 80 %.
·
If other devices, like for example decentralised inputs and outputs are connected, these
telegrams are to be considered also.
·
A bus overload for instance can be effected by an event−controlled transmission of continually
changing signals.
– Remedy: Accordingly alter the setting of the cycle time for CAN2_OUT or CAN3_OUT, so
that the total of all bus loads does not exceed the value of 80 %.
(