System bus (CAN) for Lenze PLC devices

Configuration (AIF interface)

4−10

l

PLC−Systembus EN 2.0

4.9

Diagnostics

The following codes can be used for diagnostics purposes:

Code

Information displayed

Information

C2121

AIF−CAN operating status

Chapter 4.9.1

^ 4−10

·

Settings cannot be carried out via these codes.

4.9.1

Automation interface (AIF) operating status

Via C2121 you can have the operating status of the automation interface displayed:

Code

LCD

Possible settings

Information

Lenze

Selection

C2121 AIF state

g

Bit 0

XCAN1_IN monitoring time

Bit 1

XCAN2_IN monitoring time

Bit 2

XCAN3_IN monitoring time

Bit 3

XCAN bus−off

Bit 4

XCAN operational

Bit 5

XCAN pre−operational

Bit 6

XCAN warning

Bit 7

Internally assigned

AIF status, bit−coded

·

Detailed information on this can
be found in the description for
the corresponding fieldbus
module.

C2121

Operating status

Information

Bit4 = 1 Operational

The system bus is fully functional. The PLC can transmit and receive parameter and process data.

Bit5 = 1 Pre−operational

The PLC can transmit and receive parameter data. Process data, however, are ignored.
A status change from Pre−Operational to Operational can be effected by:

·

the CAN master

^ 4−2

·

a reset node

– via C0358, if the PLC has been configured as a "quasi" master.

^ 3−8

– via the binary input signal "Reset node" at the CAN_Management SB

^ 7−20

Bit6 = 1 Warning

The PLC has received faulty telegrams and is only involved in the system bus passively, i. e. no data can be
sent from the PLC anymore.
Possible causes:

·

Missing bus termination

·

Non−sufficient shielding

·

Differences in potential with regard to the earth connection of the control electronics

·

Bus load too high

·

PLC is not connected to the system bus.

Bit3 = 1 Bus−off

The PLC has disconnected from the system bus due to too many faultily received telegrams.

·

The response to this status can be configured via C2382/4.

^ 4−9