5 network management (nmt), Network management (nmt), Pter 2.5 – Lenze DDS System bus CAN for PLC User Manual

Page 18: System bus (can) for lenze plc devices, General information

Advertising
background image

System bus (CAN) for Lenze PLC devices

General information

2−6

l

PLC−Systembus EN 2.0

2.5

Network management (NMT)

The CAN telegram for the network management is structured as follows:

11bit

2 bytes user data

Identifier

Command

Device address

00000000000

·

By means of this telegram the master can carry out state changes for the entire CAN network.

Byte 1: command

Command

(hex)

Network status

after change

Information

01

Operational

The PLC can receive parameter and process data.

02

Stopped

The PLC can receive network management telegrams, parameter and process data, however, cannot be
received.

80

Pre−operational

The PLC can receive parameter data. Process data, however, are ignored.

81

Initialisation

Reset rode: Changes with regard to the communication−relevant parameters of the system bus (e. g. CAN
address, CAN baud rate, etc.) only are accepted after a reset node.

82

Byte 2: device address

Device address Information

0

All nodes on the bus are addressed. By this, a state change can be carried out simultaneously for all devices.

1...63

Node address of the node for which a state change is to be effected.

Advertising