2 bus off, 3 response for system bus fault messages, Bus off – Lenze DDS System bus CAN for PLC User Manual

Page 59: Response for system bus fault messages, System bus (can) for lenze plc devices, Configuration (aif interface)

Advertising
background image

System bus (CAN) for Lenze PLC devices

Configuration (AIF interface)

4−9

l

PLC−Systembus EN 2.0

4.8.2

Bus off

If the PLC has disconnected from the system bus due to too many incorrectly received telegrams,
the signal "BusOffState" (CE14) is set.

The response to this can be configured via C2382/4:

Code

LCD

Possible settings

Information

Lenze

Selection

C2382

4

XCAN Conf. CE

0

0

Off

1

Controller inhibit

2

Quick stop (QSP)

Configuration of XCAN monitoring
"BusOffState"

·

Controller inhibit or quick stop
(QSP) can only be carried out for
9300 Servo PLC and ECSxA!

Tip!

Possible causes for incorrectly received telegrams can be:

·

Missing bus termination

·

Non−sufficient shielding

·

Differences in potential with regard to the earth connection of the control electronics

·

Bus load too high. See chapter 3.13.3, "Bus load by the PLC".

(

^ 3−15)

4.8.3

Response for system bus fault messages

Overview of the system bus error sources registered by the PLC and of the possible settings for the
corresponding response:

Fault message

Possible settings/response

Display

Error No.

Meaning

CINH

Fault/QSP

Off

Code

XCAN Conf. CE

1)

XCAN1_IN communication error
(time monitoring can be set via C2357/1)

ь

ь

©

C2382/1

XCAN Conf. CE

1)

XCAN2_IN communication error
(time monitoring can be set via C2357/2)

ь

ь

C2382/2

XCAN Conf. CE

1)

XCAN3_INcommunication error
(time monitoring can be set via C2357/3)

ь

ь

C2382/3

XCAN Conf. CE

1)

BUS−OFF state
(too many faulty telegrams were received)

ь

ь

C2382/4

1)

Not available; status can be determined via C2121.

^ 4−10

• Lenze setting

ü Possible