System bus (CAN) for Lenze PLC devices

"CAN" system bus interface configuration

3−12

l

PLC−Systembus EN 2.0

3.12.3

Time−out when remote parameterisation is activated

If a time−out occurs during the remote parameterisation (gateway function) activated via C0370, the
system error message CE5 is output.

The response to this can be configured via C0603:

Code

LCD

Possible settings

Information

Lenze

Selection

C0603 MONIT CE5

3

System bus: Monitoring
configuration
Time−out when remote
parameterisation is activated
(C0370)

0

TRIP

2

Warning

3

Off

3.12.4

Response in the case of system bus fault messages

Overview of the system bus error sources registered by the PLC and of the possible settings for the
corresponding response:

Fault message

Possible settings/response

Display

Error
No.

Meaning

TRIP

Message Warning

Fault/QS
P

Off

Code

CE1

62

CAN1_IN communication error
(time monitoring can be set via C0357/1)

ь

ь

C0591

CE2

63

CAN2_IN communication error
(time monitoring can be set via C0357/2)

ь

ь

C0592

CE3

64

CAN3_IN communication error
(time monitoring can be set via C0357/3)

ь

ь

C0593

CE4

65

BUS−OFF state
(too many faulty telegrams were received)

ь

ь

C0595

CE5

66

CAN time−out
(gateway function C0370)

ь

ь

C0603

• Lenze setting

ü Possible
− Not possible